Smoke-extraction flap SHEV Flap-Sonder
SHEV-FLAP smoke extraction device, made to measure
with SHE-linear actuator with integrated electronic load cut-off
The smoke extraction element SHEV-FLAP is the ideal closure for openings in flat roofs. These are especially openings above elevator shafts, which are intended for natural ventilation and smoke extraction. It can also be used as a relief opening for pressure ventilation systems in stairwells. The SHEV-FLAP consists of a straight, 50 cm high thermally insulated upstand and an integrated, tested NRWG lamella element with attached weather protection lamella hood. During construction, special attention was paid to a clean thermal separation in terms of building physics. The element is available in various standard sizes as well as made to measure. This solution provides a weather-protected opening, which ensures smoke extraction independent of wind direction.
Technical data:
Operating voltage: 24 V DC /±15%
rated current: 1 A
Duty cycle: 30% (ON: 3 min / OFF: 7 min)
Push force: 1000 N
Pulling force: 1000 N
stroke length: 48 mm
Temperature range: -5°C to + 40°C
Geometric cross section: made to measure
Manufacturer:
SIMON PROtec Systems GmbH
Type: SHEV-FLAP-Sonder
Item number: M2 1795
- Do you have any questions concerning this product?
- Sicherheitshinweise & Gewährleistungsbedingungen
- Produktinformation EA-LS-1000-48-02
- Product information EA-LS-1000-48-02
- Katalog (Web) RWA & Lüftung
- Catalogue (web) Smoke & Daily Vent
- Environmental Product Declaration (EPD)
- Safety instructions and warranty conditions
- Broschüre Fensterautomation
- Brochure Window Automation
- Umweltproduktdeklaration (EPD)
- Further products by SIMON PROtec
Matchcode | SHEV Flap-Sonder |
Article name | Entrauchungselement SHEV Flap-Sonder |
Part number | M2 1795 |
Input voltage | 24 V DC |
Nominal current | 1 |
Stroke | 48 |
Cut-Off | elektr. Lastabschaltung |
Weight | 62 |
Environment temperature range | -5 °C - 40 °C |
Product Information
Brochure SHEV-FLAP_DE_EN.pdf | Brochure for the smoke extraction element SHEV-FLAP for wind direction and weather-independent ventilation of hoistways (English/German) |
Brochure SHEV-FLAP_EN | Product information for the smoke extraction element SHEV-FLAP for wind direction and weather-independent ventilation of hoistways (English) |
Brochure Window Automation | Brochure Window Automation |
Catalogue (web) Smoke & Daily Vent | Catalogue (web) Smoke & Daily Vent |
User Manuals
Operating manual_SHEV-FLAP | Operating manual for the smoke extraction element SHEV-FLAP |
Product information EA-LS-1000-48-02 | Product information for the slit actuator EA-LS-1000-48-02 for the louvre element TG-24 |
Certificates
Environmental Product Declaration (EPD) | Environmental Product Declaration (EPD) |
Other
Safety instructions and warranty conditions | Safety instructions and warranty conditions |